Section 6 Retrofitting the Rosemount 1151
Transmitter
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6-1
Retrofitting Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6-2
Removing the Analog Electronics Assembly . . . . . . . . . page 6-2
Installing the Smart Retrofit Kit . . . . . . . . . . . . . . . . . . . . . page 6-10
Characterization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6-12
OVERVIEW This section describes how the Rosemount Smart Retrofit Kit can be used to
retrofit a Rosemount 1151AP, DP, GP, HP, or LT transmitter with
4-20 mA dc linear or square root output.
NOTE
The Rosemount 1151DR (Draft Range) Transmitter cannot be retrofitted with
the 1151-0935-0001 Retrofit Kit. In addition, Rosemount 1151 transmitters
with serial numbers below 10,000 and Rosemount 1151 AP Range Code 4
Transmitters with serial numbers between 1,318,500 and 1,690,000 may
experience some degradation in performance from temperature effect if
retrofitted. Therefore, retrofitting of these transmitters is not recommended.
SAFETY MESSAGES
Warnings ( ) Procedures and instructions in this section that raise potential safety issues
are indicated by a warning symbol ( ). Refer to the following warning
messages before performing an operation preceded by this symbol.
Explosions can result in serious injury or death. Before connecting a
communicator in an explosive atmosphere, make sure the instruments in the loop
are installed in accordance with intrinsically safe or nonincendiary field wiring
practices.
Toxic processes can result in serious injury or death. Transmitter can contain
residue process. Use appropriate safety precautions when opening drain vents or
disconnecting a transmitter from a process.
DO NOT attempt to loosen drain vent valves or disconnect the transmitter from
the process without taking precautionary measures.
Install and tighten all four process adapter bolts or drain vent valves before
applying pressure.
Both transmitter covers must be fully engaged to meet explosion-proof
requirements.