EbV Product documentation THETA NORM/UNIT
5-7
Setting range P1(P2, P3) / 0.5 ... 24 h from the current time
P1 (P2, P3)
Program-controlled restart of the heating operation. After activating the absent mode
the heating mode is interrupted until the next switch-on time of the current automatic
program P1 (as well as P2 or P3 if enabled).
0.5 ... 24 h
The set value is added to the current time and represents the return time. When
activating the absent mode again, the last set value is saved and set as the new
default value.
Display An active absent mode appears on the basic display with the indication of the return
time.
5.1.2.5.3 Party Mode (Short-term Program)
This program provides for a one-time intermediate heating of all the heating circuits
up to a specified time and skips a forthcoming or an active absent cycle completely
or partially. After the set time period, the heating circuits automatically switch back to
the operating mode which was active before the party mode. Short-term programs
such as ABSENT or HOLIDAY are skipped.
Application One-time unscheduled extension of the heating or intermediate heating during
reduced mode
Setting see 5.1.2.5 key "Operating mode" (basic display)
Earlier termination An active party mode can be terminated prematurely. Simply press the "operating
mode" ¢ key and turn the rotary pushbutton to adjust to automatic mode.
Factory setting P1 after activation
Setting range P1(P2, P3) / 0.5 ... 24 h from the current time
P1 (P2, P3)
Program-controlled restart of the heating operation. After activating the party mode
the heating mode is continued until the next switch-on time of the current automatic
program P1 (as well as P2 or P3 if enabled).
0.5 ... 24 h
The set value is added to the current time and represents the end of the party time.
When activating the party mode again, the last set value is saved and set as the new
default value.
Display An active party mode appears on the basic display with the indication of the duration
of the party.
PARTY TIL
19 .20
2.30

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rotex Controller Series and is the answer not in the manual?

Rotex Controller Series Specifications

General IconGeneral
BrandRotex
ModelController Series
CategoryController
LanguageEnglish

Related product manuals