Control during the
holiday mode If outdoor temperatures are below the frost limit (see menu "System-
parameter - Parameter 5 = plant frost protection"), the heating circuits
without wall modules
are controlled according to a reduced specified room temperature of 3 °C.
with wall modules
are controlled according to their individual frost protection limit of the heating circuit
(see menu "Unmixed- or mixed circuit -Parameter 8 = Room frost protection limit") of
10 °C.
Setting see 5.1.2.5 key "Operating mode" (basic display)
Earlier termination An active holiday mode can be terminated after an early return. Simply press the
"operating mode" ¢ key and turn the rotary pushbutton to adjust to automatic mode.
Factory setting Current date
Setting range Current date ... Current date + 250 days
Display An active holiday program appears on the basic display with the indication of the
return date.
5.1.2.5.2 Absent Mode (Short-term Program)
The operating mode ABSENT causes the heating operation to be switched off
temporarily with frost protection. During the absence, all heating circuits are
controlled according to the set reduced room temperature. After the set time period,
the heating circuits automatically switch back to the operating mode which was active
before the absence. Short-term programs such as PARTY or HOLIDAY are skipped.
Application Short absence during the heating season
Setting see 5.1.2.5 key "Operating mode" (basic display)
Earlier termination An active absence mode can be terminated after an early return. Simply press the
"operating mode" ¢ key and turn the rotary pushbutton to adjust to automatic mode.
Factory setting P1 after activation
ABSENT TIL
20 .10