Section 2 Installation H85A Manual
www.rottlermfg.com
2-14
Power Supply
This machine has the following power requirements:
• 208 to 240 VAC
• Single or Three Phase Power
• 50 or 60 Hz
• 25 Amps
See illustration below for correct connection of incoming power. Measured power at the machine’s
main breaker must be within the required range listed above. If incoming power is not within range, a
transformer must be used. Failure to do so will cause the machine to function abnormally and cause
permanent damage to the electronic control system.
Some electrical services contain a “Hot Leg, High Leg, or Wild Leg”, where one leg measures 208VAC
to Ground instead of 120VAC. Use of the “Hot Leg, High Leg, or Wild Leg” is NOT permitted on this
machine. If a “Hot Leg, High Leg, or Wild Leg” is present, connect the machine in the Single Phase
conguration shown below.
Electrically connect in accordance with national and local electrical
codes.
Do not attempt to connect more 240VAC to this machine.