LED module status
Ethernet IP setting
For Ethernet IP, it is necessary to set an IP address and a subnet mask.
The IP address must be in the same range as the IP address of the PLC system.
These parameters can be set on page 17 of the Configuration menu on the Cyclomix
®
Evo.
For EtherNet IP, the characteristics of a device are stored in an ASCII data file with the suffix EDS. This file is used by
the PLC configuration tools when setting up the network configuration, (with instance ID for PLC input =100, and
instance ID for PLC output =150).
This configuration file can be downloaded from www.sames.com
LED status Description
Off No power
Green
Controlled by a working scanner and, if CIP Sync is enabled, the time is synchronized with a Grand-
master clock.
Green, flashing
Not configured, Scanner in standby state, or, if CIP Sync is enabled, the time is synchronized with the
Grandmaster clock.
Red Major fault (EXCEPTION status, FATAL error, etc.)
Red, flashing Recoverable Fault(s).
The module is configured, but the saved settings differ from the settings currently in use.