EB 5573-1 EN 143
Appendix
F Function WE System
Comments
Function block parameters: value range (default setting)
13 Flow rate
limitation in
RK2
0
Anl 3.0,
4.x, 10.0,
11.x
CO6 > F13 - 1: Flow rate limitation (only with CO6>F10- 1
and when WMZ2 is activated)
Function block parameters:
Max. limit/0.01 to 650m³/h (1.5m³/h)
Limiting factor/0.1 to 10 (1)
14 Capacity
limitation in
RK2
0
Anl 3.0,
4.x, 10.0,
11.x
CO6 > F14 - 1: Capacity limitation (only with CO6>F10- 1
and when WMZ2 is activated)
Function block parameters:
Max. limit/0.1 to 6500kW (1.5kW)
Limiting factor/0.1 to 10 (1)
* Not systems Anl 1.0, 1.5–1.9, 3.0, 3.5, 4.0, 10.0, 11.x
F Function block number, WE Default setting, Anl System code number
CO8 > Initialization of BI1 and BI2 (all systems)
F Function WE System
Comments
Function block parameters: value range (default setting)
01 Analysis of BI1 0
All
CO8 > F01 - 1: Analysis active
Function block parameters:
Error message when BI = 0, BI = 1, none (1)
02 Analysis of BI2 0
All
CO8>F02 - 1: Analysis active
Function block parameters:
Error message when BI = 0, BI = 1, none (1)