EB 5573-1 EN 145
Appendix
P Display reading Parameter: Value range (default setting)
06
Min. ow temperature:
–5.0 to 150.0°C (20.0°C)
07
Max. ow temperature:
–5.0 to 150.0°C (90.0°C)
–5.0 to 50.0°C (50.0°C) with CO1 > F05 - 1
09
Outdoor temperature for continuous day mode:
–50.0 to 5.0°C (–15°C)
10
Minimum ow temperature set point HC for binary demand
processing:
5.0 to 150.0°C (40.0°C)
11
Return ow gradient:
0.2 to 3.2 (1.2)
12
Return ow level:
–30.0 to 30.0°C (0.0°C)
13
Base point for return ow temperature:
5.0 to 90.0°C (65.0°C)
14
Max. return ow temperature:
5.0 to 90.0°C (65.0°C)
15
Set point boost (pre-control circuit):
0.0 to 50.0°C (5.0°C)
PA2: Heating circuit HC2
P Display reading Parameter: Value range (default setting)
01
Flow gradient:
0.2 to 3.2 (1.8)
0.2 to 1.0 (1.0) with CO1, 2 > F05 - 1
02
Level (parallel shift):
–30.0 to 30.0°C (0.0°C)
03
Flow set point (day)
(only with CO1 > F02 - 0 and CO1 >
F09 - 1):
–5.0 to 150.0°C (50.0°C)

Table of Contents