146 EB 5573-1 EN
Appendix
P Display reading Parameter: Value range (default setting)
04
Flow set point (night)
(only with CO1 > F02 - 0 and CO1 >
F09 - 1):
–5.0 to 150.0°C (30.0°C)
05
Four-point characteristic
Outdoor temperature:
–50.0 to 50.0°C (–15.0°C, –5.0°C, 5.0°C, 15.0°C)
with CO2 > F04 -1: (5°C, 15°C, 25°C, 30°C)
Flow temperature:
–5.0 to 150.0°C (70.0°C, 55.0°C, 40.0°C, 25.0°C)
with CO2 > F04 -1: (20°C, 15°C, 10°C, 5°C)
Reduced ow temperature:
–5.0 to 150.0°C (60.0°C, 40.0°C, 20.0°C, 20.0°C)
with CO2 > F04 -1: (30°C, 25°C, 20°C, 15°C)
Return ow temperature:
5.0 to 90.0°C (65.0°C, 65.0°C, 65.0°C, 65.0°C)
06
Min. ow temperature:
–5.0 to 150.0°C (20.0°C)
07
Max. ow temperature:
–5.0 to 150.0°C (90.0°C)
–5.0 to 50.0°C (50.0°C) with CO1 > F05 - 1
09
Outdoor temperature for continuous day mode:
–50.0 to 5.0°C (–15°C)
11
Return ow gradient:
0.2 to 3.2 (1.2)
12
Return ow level:
–30.0 to 30.0°C (0.0°C)
13
Base point for return ow temperature:
5.0 to 90.0°C (65.0°C)
14
Max. return ow temperature:
5.0 to 90.0°C (65.0°C)