EB 5573-1 EN 147
Appendix
PA4: Domestic hot water heating (DHW)
P Display reading Parameter: Value range (default setting)
01
Min. adjustable DHW set point:
5.0 to 90.0°C (40.0°C)
02
Max. adjustable DHW set point:
5.0 to 90.0°C (90.0°C)
03
Hysteresis:
1.0 to 30.0°C (5.0°C)
04
Charging temperature boost:
0.0 to 50.0°C (10.0°C)
05
Max. charging temperature (only with CO4 > F05
- 1)
:
20.0 to 150.0°C (80.0°C)
06
Lag time for storage tank charging pump = Valve transit time x
P06:
0.0 to 10.0 (1.0)
07
Max. return ow temperature:
20.0 to 90.0°C (65.0°C)
10
Solar circuit pump ON:
1.0 to 30.0°C (10.0°C)
11
Solar circuit pump OFF:
0.0 to 30.0°C (3.0°C)
12
Max. storage tank temperature:
20.0 to 90.0°C (80.0°C)
PA5: System-wide parameters
P Display reading Parameter: Value range (default setting)
01
Start temperature for boiler pump (system Anl 16.x only)
20.0 to 90.0°C (60.0°C)
02
Boiler pump hysteresis (system Anl 16.x only)
0.0 to 30.0°C (5.0°C)