148 EB 5573-1 EN
Appendix
PA6: Modbus
P Display reading Parameter: Value range (default setting)
01
Modbus station address (8 bit):
1 to 246 (255)
1 to 3200 (255) with CO6 > F02 - 1
03
Modem init. time:
1 to 255min (1min)
04
Modem dialing pause (P):
0 to 255min (5min)
05
Modem timeout (T):
1 to 255min (5min)
06
Number of redialing attempts:
1 to 255 (15)
07
Phone number of control station:
Max. 22 characters; 1, 2, 3, ..., 9, 0
- for end of a string; P for pause
08
Access number:
Max. 22 characters; 1, 2, 3, ..., 9, 0
- for end of a string; P for pause
09
Mobile phone number:
Max. 22 characters; 1, 2, 3, ..., 9, 0
- for end of a string; P for pause