2: FDT-3
Activated when run frequency meets the following condition.
Active condition: Absolute value (FDT level - run frequency) ≤ FDT Bandwidth/2
Group Display Parameter Name Setting Range Default Unit
I/O group
I52
Cannot be set above Max frequency (F21).
When setting I52 and I53 to 30.0Hz and 10.0 Hz, respectively
3: FDT-4
Activated when run frequency meets the following condition.
Active condition:
Accel time: Run Frequency ≥ FDT Level
Decel time: Run Frequency > (FDT Level – FDT Bandwidth/2)
Group Display Parameter Name Setting Range Default Unit
I/O group
I52
Cannot be set above Max frequency (F21).
When setting I52 and I53 to 30.0Hz and 10.0 Hz, respectively