Santerno Sinus M - 7.2 Function group 1

Santerno Sinus M
219 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7-8
LED
display
Parameter
name
Min/Max
range
Description
Factory
defaults
Adj.
during
run
F59
[Stall
prevention
select]
0 ~ 7
This parameter stops accelerating ramp
during acceleration, decreases the
frequency during constant speed and
stops decelerating ramp during
deceleration.
0
X
During
Decel
During
constant run
During
Accel
Bit 2
Bit 1
Bit 0
0
-
-
-
1
-
-
2
-
-
3
-
4
-
-
5
-
6
-
7
F60
[Stall
prevention
level]
30 ~ 200
[%]
This parameter sets the amount of
current to activate stall prevention
function during Acceleration, Constant
speed or Deceleration.
The set value is the percentage of H33-
[Motor rated current].
150
X
F61
[When Stall
prevention
during
deceleration,
voltage limit
select]
0~1
In Stall prevention run during
deceleration, select 1if you want to limit
output voltage.
F63
[Save
up/down
frequency]
0 ~ 1
This parameter determines whether to
save the specified frequency during
up/down operation.
When 1 is selected, the up/down
frequency is saved in F64.
0
X
F64
1)
[Saved
up/down
frequency]
0 ~ 400
[Hz]
If “Save up/down frequency” is selected in
F63, this parameter shows the frequency
before the inverter stops or decelerates.
0
X
F65
[Up-down
mode select]
0~2
You can select the Up-down mode
among three options:
0
X
0
Increases goal frequency as a
standard of Max. frequency/Min.
frequency.
1
Increases as many as step
frequencies according to edge
input.
2
Available to combine 1 and 2.
1):
It is shown when F63 is set to 1.