7-9
F66
[Up-down
step
frequency]
0~400
[Hz]
In case of choosing F65 as 1 or 2, it
means increase or decrease of
frequency according to up-down input.
0.00
X
F70
[Draw run
mode
select]
0~3
0
Inverter does not run as in
draw mode
0
X
1
V1(0~10V) input
2
I(0~20mA) input
3
V1(–10~10V) input
F71
[Draw rate]
0~100
[%]
Sets rate of draw
0.00
O