EasyManua.ls Logo

Santerno Sinus M - 7.3 Function group 2

Santerno Sinus M
219 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7-15
LED
display
Parameter
name
Min/Max
range
Description
Factory
defaults
Adj.
durin
g run
H61
Sleep delay
time
0~999 (sec) Sleep Mode delay time 60 sec X
H62
Sleep
frequency
0~400Hz Sleep Frequency 0.0Hz O
H63
Wake-up
level
0~50[%] Wake Up level 2[%] O
H64
[KEB select]
0~1
Sets the KEB
0
X
H65
[KEB action
start level]
110~140[%]
Sets KEB action start level according to
level.
125.0
X
H66
[KEB action
stop level]
110~145[%]
Sets KEB action stop level according to
level.
130.0
X
H67
[KEB action
gain]
1~20000
Sets KEB action gain.
1000
X
H69
Accel/Decel
Change
Frequency
0 ~ 400Hz Accel/decel change frequency 0Hz X
H70
[Frequency
Ref. for
Accel/Decel]
0 ~ 1
0
Based on Max freq (F21)
0
X
1
Based on Delta freq.
H71
[Accel/Decel
time scale]
0 ~ 2
0
Settable unit: 0.01 second.
1
O
1
Settable unit: 0.1 second.
2
Settable unit: 1 second.
H72
[Power on
display]
0 ~ 17
This parameter selects the parameter to be
displayed on the keypad when the input
power is first applied.
0
O
0
Frequency command
1
Accel time
2
Decel time
3
Drive mode
4
Frequency mode
5
Multi-step frequency 1 (St1)
6
Multi-step frequency 2 (St2)
7
Multi-step frequency 3 (St3)
8
Output current (Cur)
9
Motor rpm (rPM)
10
Inverter DC link voltage (dCL)
11
User display select (vOL)
12
Fault display 1(nOn)
13
Operating direction select (drC)
14
Output current 2
15
Motor rpm 2
16
Inverter DC link voltage 2
17
User display select 2

Table of Contents

Other manuals for Santerno Sinus M