B 07 FMZ 1 Dimension
Range: -------t
-----.-t
----.--t
---.---t
------ t*10
----- t*100
-- -----kg
-----.-kg
----.--kg
---.---kg
Preconfigured values:-------t
B07 determines the display format for counter 1 and the impulse weight for the external
counter.
B 08 FMZ 1 impulse duration
Range: 0-1,000 ms Original value: 0 ms
If an external counter is not connected, set the parameter to 0.
B08 defines the length of an output impulse for the external totalizing counter. The weighting
of an impulse equals the smallest possible display digit of counter 1
(parameter B07).
B08<10ms:
The impulse output is blocked.
All impulses not issued yet are cleared.
The output frequency is the following at the feed rate
PNENN = Nominal feed rate (B02) in kg/h or t/h
Zmin = kleinste Anzeigestelle von Zähler 1 (B 07) in kg oder t
Smallest counter 1 display digit (B 07) in kg or t
Select a Z min (B07) so that f is no longer than 10 Hz.
Beyond this, the impulse duration has to be less than 1/f.
INTECONT® Satus Operating Manual BV-H2346GB / 0833 41