EasyManuals Logo

Schenck process Intecont Satus User Manual

Schenck process Intecont Satus
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #52 background imageLoading...
Page #52 background image
F 09 Value for V-MIN
Range: -10...200.0 % V Preconfigured value: 5.0 % V
Reference: Nominal speed B 05
Feed rate measurement is started or stopped once the belt speed reaches a speed either
greater or smaller than the limit value Vmin (v).
The measuring gives a non-averaged speed value v.
The on or off states relate to the belt drive and to the measurement of the flow rate.
Belt load and belt speed are continuously measured.
Display when ON: Rotating point in the display.
The rotational speed is approximately proportional to the feed rate,
but is never zero.
Display when OFF: After a completed measurement the point remains still.
An operative switch-off command doesn’t stop the flow rate measurement immediately;
measurement stops after an after-run time of 3s.
46 BV-H2346GB / 0833 Operating Manual INTECONT® Satus
© Schenck Process

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Schenck process Intecont Satus and is the answer not in the manual?

Schenck process Intecont Satus Specifications

General IconGeneral
BrandSchenck process
ModelIntecont Satus
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals