PART II - USER MANUAL
How to maintain a PDU?
Internal maintenance is not an option
A Schleifenbauer Intelligent PDU may not be opened by unauthorized persons. In the event of malfunction or faults in
the PDU, please refer to the warranty conditions. Schleifenbauer Products BV will not accept warranty claims if the PDU
has been opened or alterations have been made.
Please pay attention to the operation conditions before installation and operation of the Schleifenbauer PDU.
The Schleifenbauer PDU has to be protected according to the valid installation guidelines.
The rated value of the in-series protective device may not exceed the maximum value indicated on the product.
The Schleifenbauer PDU may not be used in: a humid environment, a seriously contaminated environment or
outdoors.
The manufacturer’s warranty on the Schleifenbauer PDU becomes invalid when the QC sticker on the side of the
profile is broken.
Before turning on the PDU for the first time, make sure that it has been allowed to acclimatize to the ambient
temperature for at least 24 hours. Major temperature fluctuations can lead to the formation of condensation in the
PDU if this guideline is not followed.
Please keep in mind that maximum allowed temperature for a metal enclosure is 70 °C for installation in a normal
location and 90 °C for installation in a restricted access location.
How to be sure the status of switchable outlets will not change during firmware
upgrade or restarting of the controller?
There are no extra safety precautions necessary! Because power distribution and the control over measuring and
switching is separated. This means that while updating or restarting the (controller of the) PDUs, power distribution is not
interrupted.
LIFE-SUPPORTING POLICY
The Schleifenbauer PDU has been designed for use in data centers where equipment has to meet very high demands
especially regarding to reliability.
The Intelligent PDU however may not be applied in surroundings where a malfunction in the PDU can have consequences
for life support systems.
Life support systems include any devices designated as “critical” by the U.S. FDA. Such systems are found not only in
medical environments such as hospitals, but also on offshore platforms, in petrochemical plants, in air traffic control
centers, etc.