PART I - INSTALLATION OF HARDWARE
Please use the information in this chapter to inspect, install and connect the Schleifenbauer Intelligent PDU and all
optional mentioned accessories.
The PDU must be installed in a restricted access location
Socket-outlet must be installed near the equipment
Socket-outlet must be easily accessible
Installation by expert personnel only
After installation: default passwords / RC4 keys MUST be changed (see: Part III - Administrator manual)
SAFETY WARNINGS
This manual contains important safety instructions that should be followed during installation and operation of the PDU.
Please read this manual carefully since there may be serious or fatal personal injury and damage to the equipment if the
safety instructions, warnings and directions are not followed. Please save this document for future use.
EXPERT PERSONNEL
Installation, maintenance and inspection of the Schleifenbauer Intelligent PDU must be carried out by adequately trained
persons according to NEN EN 50110-1, with full observance of the specifications of NEN EN 50110-1 and NEN 3140.
TECHNICAL INSTALLATION REQUIREMENTS
Before installing and putting the system into operation, check whether the characteristics of the electrical system to which
connection is to be made correspond to the product specifications.
The Schleifenbauer Intelligent PDU has been designed for connection to electrical systems that comply with IEC
60364 or in the Netherlands, NEN 1010.
The voltage, maximum permitted current and the number of phases must be correct. This information is
displayed on the front side of the PDU.
The maximum permitted power must be taken into account with regard to the maximum length and the diameter
of the connecting lead.
The values and characteristics of the in-series protective devices must match the PDU and the protective
elements included in it.
The environmental factors must correspond to the product specifications.
VISUAL INSPECTION
After opening the cardboard box and removing the packaging material, the PDU should be checked visually. The PDU
should not be put into operation if damage is detected such that safe and proper operation cannot be guaranteed. In such
cases, please contact Schleifenbauer Products BV.
Note that, in the case of PDUs that are equipped with an over voltage protection, the overvoltage protection and the
respective overcurrent protection (if applicable) must be inspected on a regular basis.
Page 7 of 54
V252_User manual
Schleifenbauer PDU

Table of Contents