Appendix
A.3 MODBUS
SENTRON PAC4200
228 System Manual, 09/2009, A5E02316180B-02
Offset Number of
registers
Name Format Unit Value range Access
141 2 Maximum Total Reactive Power (VARn) Float VAR - R
143 2 Maximum Total Power Factor Float - - R
145 2 Minimum Voltage a-n Float V - R
147 2 Minimum Voltage b-n Float V - R
149 2 Minimum Voltage c-n Float V - R
151 2 Minimum Voltage a-b Float V - R
153 2 Minimum Voltage b-c Float V - R
155 2 Minimum Voltage c-a Float V - R
157 2 Minimum Current a Float A - R
159 2 Minimum Current b Float A - R
161 2 Minimum Current c Float A - R
163 2 Minimum Apparent Power a Float VA - R
165 2 Minimum Apparent Power b Float VA - R
167 2 Minimum Apparent Power c Float VA - R
169 2 Minimum Active Power a Float W - R
171 2 Minimum Active Power b Float W - R
173 2 Minimum Active Power c Float W - R
175 2 Minimum Reactive Power a (VARn) Float VAR - R
177 2 Minimum Reactive Power b (VARn) Float VAR - R
179 2 Minimum Reactive Power c (VARn) Float VAR - R
181 2 Minimum Power Factor a Float - 0 ... 1 R
183 2 Minimum Power Factor b Float - 0 ... 1 R
185 2 Minimum Power Factor c Float - 0 ... 1 R
187 2 Minimum Line Frequency Float Hz 45 ... 65 R
189 2 Minimum 3-Phase Average Voltage ph-n Float V - R
191 2 Minimum 3-Phase Average Voltage ph-ph Float V - R
193 2 Minimum 3-Phase Average Current ph-ph Float A - R
195 2 Minimum Total Apparent Power Float VA - R
197 2 Minimum Total Active Power Float W - R
199 2 Minimum Total Reactive Power (VARn) Float VAR - R
201 2 Minimum Total Power Factor Float VAR - R

Table of Contents