Doc# E166703 E-10
E: Retrieving Logs
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
• Only one log at a time can be retrieved.
• First Timestamp: Timestamp of the oldest record.
• Last Timestamp: Timestamp of the newest record.
Log Retrieval Block:
The Log Retrieval Block is the main interface for retrieving logs. It is comprised of 2
parts: the header and the window. The header is used to program the particular data
the MP200 unit presents when a log window is requested. The window is a sliding
block of data that can be used to access any record in the specified log.
Session Com Port: The MP200 unit's Com Port which is currently retrieving logs.
Only one Com Port can retrieve logs at any one time.
Registers: 0xC34E - 0xC34E
Size: 1 register
0 No Session Active
1 COM1 (RS485/Ethernet/WiFi)
2COM2 (USB)
3 COM3 (RS485)
To get the current Com Port, see the NOTE on querying the port, on the previous
page.