Doc# E166703 2-15
2: MP200 Metering System Overview and Specifications
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Switching rate max.: 10/s
Mechanical life: 5 x 10
7
switching operations
Electrical life: 10
5
switching operations at rated
current
Breakdown voltage: AC 1000 V between open contacts
Isolation: AC 3000 V / 5000 V surge system
to contacts
Reset/power down state: No change - last state is retained
Inputs:
Number of inputs: 4
Sensing type: Wet or dry contact status detection
Wetting voltage: DC (1-24) V, internally generated
Input current: 2.5 mA – constant current regu-
lated
Minimum input voltage: 0 V (input shorted to common)
Maximum input voltage: DC 150 V (diode protected against
polarity reversal)
Filtering: De-bouncing with 50 ms delay time
Detection scan rate: 100 ms
Isolation: AC 2500 V system to inputs
External Connection: AWG 12-26/(0.129 - 3.31) mm
2
11 pin, 0.200” pluggable terminal
block
Mechanical Parameters
Dimensions: 7.6(L) x 11.28(W) x 4.36(H) in /
19.3(L) x 28.65(W) x 11.07(H) cm
Weight: 7 pounds (3.18 kg)