Doc# E166703 2-14
2: MP200 Metering System Overview and Specifications
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Optional:
Ethernet/WiFi port (Com 1) 802.11b Wireless or RJ45
Connection 10/100BaseT Ethernet
Com Specifications
RS485 Ports (Com 1 and Com3):
RS485 Transceiver; meets or exceeds EIA/TIA-485 Standard
Type: Two-wire, half duplex
Min. input impedance: 96 kΩ
Max. output current: ±60 mA
Protocol: Modbus RTU, Modbus ASCII
Com port baud rates: 9600 to 57600 bps
Device address: 001-247
Data format: 8 Bit
WiFi/Ethernet Port (optional Com 1):
Wireless security: 64 or 128 bit WEP; WPA; or WPA2
Protocol: Modbus TCP
Device address: 001-247
USB Port (Com 2):
Protocol: Modbus ASCII
Com port baud rate: 57600 bps
Device address: 1
Relay Output/Digital Input Board Specifications at 25 °C
Relay outputs:
Number of outputs: 2
Contact type: Changeover (SPDT)
Relay type: Mechanically latching
Switching voltage: AC 150 V / DC 30 V
Switching power: 750 VA / 150 W
Switching current: 5 A