Select a sensor type using the Rotary switch (SW303) and DIP switch (SW304).
Default value: K -200 to 1370
Note: If the input type is changed, Scaling high/low limit, External setting input
high/low limit (optional), Transmission output high/low limit (optional)
will become the altered input range high/low limit value.
(Table 3.2-2)
Rotary
SW303
No.
DIP
SW304
No. 7
Sensor type
Scale range (DIP SW304 No.6)
OFF ON
0 OFF K -200 to 1370 -320 to 2500
1 OFF J -200 to 1000 -320 to 1800
2 OFF R 0 to 1760 0 to 3200
3 OFF B 0 to 1820 0 to 3300
4 OFF PL- 0 to 1390 0 to 2500
5 OFF N 0 to 1300 0 to 2300
6 OFF Pt100 -199.9 to 850.0 -199.9 to 999.9
7 OFF JPt100 -199.9 to 500.0 -199.9 to 900.0
0 ON S 0 to 1760 0 to 3200
1 ON E 0 to 1000 0 to 1800
2 ON T -199.9 to 400.0 -199.9 to 750.0
3 ON C (W/Re5-26) 0 to 2315 0 to 4200
4 ON 4 to 20mA DC -1999 to 9999
5 ON 0 to 20mA DC -1999 to 9999
6 ON 0 to 1V DC -1999 to 9999
7 ON Pt100 -200 to 850 -320 to 1560