OPERATING INSTRUCTIONS | LFP CUBIC 8019918/ZJA6 / 2017-07-20 | SICK AG
Subject to change without notice
30
8 OPERATION
8.2.2 Normally open with adjustable hysteresis
Applications
Dry run protection
Empty signal
Conguration
1. Congure the Qx switching output as normally open.
Set the parameter in the QxMENU-OUx menu to Qx_Hno.
2. Set the switching point.
Set the value in the QxMENU-SPx menu to the level in mm (e.g. 500 mm).
3. Set the reset point.
Set the value in the QxMENU-RPx menu to the level in mm (e.g. 450 mm).
4. Select the electrical property (NPN/PNP/DRV (push/pull)).
Select the parameter in the QxMENU-TYPx menu.
The following rules apply:
Qx-PNP = Switching output in PNP circuit
Qx-NPN = Switching output in NPN circuit
Qx-Drv = Switching output in push/pull function
Switching output behavior
SP
RP
Active
Error signal
Inactive
Level
t
Switching output PNP NPN DRV Error status
Normally open/HNO
active U
v
0 V U
v
(PNP switched)
inactive
inactive 0 V
1)
U
v
2)
0 V (NPN switched)
1)
Pulldown only.
2)
Pullup only.