8 OPERATION
8.2.6 N/O output with error signal
Application
If there is an error message at the LFP, this can be transferred using a switching contact.
Conguration
1. Congure the Qx switching output as normally open.
• Set the parameter in the QxMENU-OUx menu to Qx_Eno.
2. Select the electrical property (NPN/PNP/DRV (push/pull)).
Select the parameter in the QxMENU-TYPx menu.
The following rules apply:
• Qx-PNP = Switching output in PNP circuit
• Qx-NPN = Switching output in NPN circuit
• Qx-Drv = Switching output in push/pull function
8.2.7 N/C output with error signal
Application
If there is an error message at the LFP, this can be transferred using a switching contact.
Conguration
1. Congure the Qx switching output as normally closed.
• Set the parameter in the QxMENU-OUx menu to Qx_Enc.
2. Select the electrical property (NPN/PNP/DRV (push/pull)).
Select the parameter in the QxMENU-TYPx menu.
The following rules apply:
• Qx-PNP = Switching output in PNP circuit
• Qx-NPN = Switching output in NPN circuit
• Qx-Drv = Switching output in push/pull function