Figure 29: Measuring the output signal in VDC
1. Switch the measuring range of the multimeter to VDC.
2. Connect the multimeter to the signal lead and 0 V lead.
3. Connect the voltage supply (+12/24 V).
4. Connect 0 V (-0 V).
Measuring the 4 ... 20 mA output signal
Figure 30: Measuring the output signal in mA
1. Switch the measuring range of the multimeter to mA.
2. Connect the multimeter to the signal lead and 0 V lead.
3. Connect the voltage supply (+12/24 V).
4. Connect 0 V (-0 V).
Alternative measuring method: using a resistor (e. g., 100 W):
Figure 31: Measuring the output signal using a resistor
1. Connect the resistor to the signal lead and 0 V lead.
2. Switch the measuring range of the multimeter to VDC.
3. Connect the multimeter in parallel to the resistor.
When using a resistor of, for example, 100 W, the following values are displayed:
Table 39: Example measurement values
Supply at 4 mA (null zone) at 20 mA (end position)
12 V, 24 V 0.4 V 2 V
7.3 Repairs
All repair work on the device must be carried out by SICK Service.