Operation
MCS100FT · Operating Instructions · 8011893 V2-1 · © SICK AG 79
Subject to change without notice
5.8.8 Maintenance
Menu: FID-100FT/Maintenance
5.8.8.1 Ignition
Menu: FID-100FT/Maintenance/Ignition
The FID ignites automatically during start-up.
This menu serves to start ignition manually.
The LED goes on when the flame is burning.
If the FID does not ignite
p. 96, §8.6
5.8.8.2 Maintenance mode
Menu: FID-100FT/Maintenance/Maintenance mode
This menu serves to switch the operating state from “Measuring” to “Maintenance” (and
vice-versa).
In “Maintenance”, maintenance mode is just signaled and the FID-100FT continues to run.
Parameter data are blended in automatically.
Designation Remark
Measuring Select operating state “Measuring”
Process “Internal process” display (for information only)
Maintenance mode LED on: Operation mode “Maintenance” active
Service mode leaving Delay time until the FID-100FT switched automatically to
Measuring mode.
lock-in Maintenance mode cannot be exited.
Please contact SICK Customer Service.
Maintenance mode Select Maintenance mode
Ignition
Maintenance mode
Test gas switch
/FID-100FT/Maintenance/
SCU
FID-100FT
Measure
p. 79, §5.8.8.1
p. 79, §5.8.8.2
p. 80, §5.8.8.3
/FID-100FT/Maintenance/Ignition
SCU
FID-100FT
Measure
Flame burning
Ignition
Process
Execute
Start
Measuring
Maintenance mode
/FID-100FT/Maintenance/Maintenance mode/
SCU
FID-100FT
Measure
Maintenance mode
Service mode leaving
Switching on
lock-in
Save
Maintenance mode