7SR210 Settings Guide
Unrestricted ©2018 Siemens Protection Devices Limited Page 9 of 61
Description Range Default
Gn Under Current
When set to Disabled, no Under Current elements will be functional and all
associated settings will be hidden. (The Setting Dependencies setting being set to
Disabled will make all settings visible but will not allow them to operate).
Enabled, Disabled Disabled
Gn Thermal
When set to Disabled, no Thermal elements will be functional and all associated
settings will be hidden. (The Setting Dependencies setting being set to Disabled
will make all settings visible but will not allow them to operate).
Enabled, Disabled Disabled
Gn CT Supervision
When set to Disabled, no CT Supervision elements will be functional and all
associated settings will be hidden. (The Setting Dependencies setting being set to
Disabled will make all settings visible but will not allow them to operate).
Enabled, Disabled Disabled
Gn CB Fail
When set to Disabled, no CB Fail elements will be functional and all associated
settings will be hidden. (The Setting Dependencies setting being set to Disabled
will make all settings visible but will not allow them to operate).
Enabled, Disabled Disabled
Gn Broken Conductor
When set to Disabled, no Broken Conductor elements will be functional and all
associated settings will be hidden. (The Setting Dependencies setting being set to
Disabled will make all settings visible but will not allow them to operate).
Enabled, Disabled Disabled
Gn Trip Cct Supervision
When set to Disabled, no Trip Cct Supervision elements will be functional and all
associated settings will be hidden. (The Setting Dependencies setting being set to
Disabled will make all settings visible but will not allow them to operate).
Enabled, Disabled Disabled
Gn Close Cct Supervision
When set to Disabled, no Close Cct Supervision elements will be functional and all
associated settings will be hidden. (The Setting Dependencies setting being set to
Disabled will make all settings visible but will not allow them to operate).
Enabled, Disabled Disabled
Gn Inrush Detector
When set to Disabled, no Inrush Detector elements will be functional and all
associated settings will be hidden. (The Setting Dependencies setting being set to
Disabled will make all settings visible but will not allow them to operate).
Enabled, Disabled Disabled
Gn CB Counters
When set to Disabled, no Gn CB Counter elements will be functional and all
associated settings will be hidden. (The Setting Dependencies setting being set to
Disabled will make all settings visible but will not allow them to operate).
Enabled, Disabled Disabled
Gn I^2t CB Wear
When set to Disabled, no Gn I^2t CB Wear elements will be functional and all
associated settings will be hidden. (The Setting Dependencies setting being set to
Disabled will make all settings visible but will not allow them to operate).
Enabled, Disabled Disabled
Gn Arc Flash Detector
When set to Disabled, no Arc Flash Detector elements will be functional and all
associated settings will be hidden. (The Setting Dependencies setting being set to
Disabled will make all settings visible but will not allow them to operate).
Enabled, Disabled Disabled