7SR210 & 7SR220 Description of Operation
Unrestricted  Page 92 of 94 ©2018 Siemens Protection Devices Limited
6.3.8 Fault Locator
The  relay  provides  a  single-end  type  fault  locator  which  is  able  to  estimate  the  fault  position  using
analogue  information  measured  by  the  relay  at  one  end  of  the  protected  circuit  during  the  short
duration of the fault.
Following relay operation due to a system fault, the fault waveform record is automatically evaluated to
establish the fault type in terms of the phase(s) affected and the relevant current and voltage is used
to  calculate  the  fault  impedance.  The  relay  compares  this  information  to  a  line  model  based  on
characteristic impedance parameters which are input to the relay  as settings and provides an output
estimate  of  the fault location. This  data is presented as  a  percentage  of  line length  or a  distance in
miles or kilometres.
The Positive Sequence Impedance on the protected line must be provided to the relay as settings for
impedance magnitude and characteristic phase angle to enable the distance to fault to be calculated.
The  Earth  Fault  return  impedance  is  specified  in  terms  of  the  ratio  of  zero  to  positive  sequence
impedance  magnitudes  and  the  characteristic  phase  angle  of  the  zero  sequence  impedance.  The
characteristic  angle  of  the  zero  sequence  impedance  is  often  significantly  different  to  that  of  the
positive sequence impedance.
When power systems are earthed through compensation (Peterson) coils, the earth fault currents are
extremely  low  and  are  not  proportional  to  fault  location.  Impedance  based  fault  location  cannot  be
used  for  earth faults. Phase-to-phase fault  location  can  be  estimated. On  networks  of  this type  it  is
possible to have two earth-faults on the network simultaneously on different phases of the same circuit
which will appear as a phase-to-phase fault. This is known as  a Cross-Country  fault. In these cases
the  measured impedance  cannot  give  an accurate estimate  of  the fault  condition.  The  7SR22  relay
provides  detection of this condition using the measured zero sequence voltage to positive sequence
voltage  ratio  (U0/U1)  to  allow  the  possible  cross-country  fault  to  be  reported.  This  threshold  is
adjustable by a user setting.
Fault Location is reported for faults calculated in a zone which extends  to 200 %  of the forward line
impedance  and 10 %  in the  reverse  direction.  High resistance  fault  results where fault  resistance  is
calculated  as  up  to  20  times  the  line  impedance  are  reported.  For  faults  beyond  these  limits,  the
message ‘No Location’ is reported.
The  Fault Location  estimation  is initiated by  operation  of the Trip  Output.  Some  protection  elements
may  be  set  to  provide  tripping  for  system  conditions  where  a  fault  location  is  not  applicable.  The
initiation of the Fault Locator can be inhibited by user settings.
The settings for the Fault Locator are found as a sub-menu in the Data Storage menu.
The  Fault  Locator  result  data is  available in the Fault  Data records  and  can  be  viewed at  the  relay
fascia and downloaded from the relay.
6.4  Metering
The metering feature provides real-time data available from the relay fascia in the ‘Instruments Mode’ or via the
data communications interface.
The Primary values are calculated using the CT and VT ratios set in the CT/VT Config menu.
The text displayed in the relays ‘Instruments Mode’ associated with each value can be changed from the default
text using the Reydisp software tool.
The user can add the meters that are most commonly viewed to a ‘Favourites’ window by pressing the ‘ENTER’
key  when  viewing  a  meter.  The  relay  will  scroll  through  these  meters  at  an  interval  set  in  the System
Config/Favourite Meters Timer menu.