7SR220 Settings Guide
Unrestricted ©2018 Siemens Protection Devices Limited Page 71 of 107
Description Range Default
Clock Sync.
Selects which input is used to synchronise the real time clock
Combination of ( BI1, BI2, BI3, BI4,
BI5, BI6, BI7, BI8, BI9, BI10, BI11,
BI12, BI13, V1, V2, V3, V4, V5, V6,
V7, V8, V9, V10, V11, V12, V13,
V14, V15, V16 )
----------------------
-------
Reset LEDs & O/Ps
Selects which inputs will reset the latched LEDs and binary
outputs
Combination of ( BI1, BI2, BI3, BI4,
BI5, BI6, BI7, BI8, BI9, BI10, BI11,
BI12, BI13, V1, V2, V3, V4, V5, V6,
V7, V8, V9, V10, V11, V12, V13,
V14, V15, V16 )
----------------------
-------
Inverted Inputs
Selects which inputs will be inverted
Combination of ( BI1, BI2, BI3, BI4,
BI5, BI6, BI7, BI8, BI9, BI10, BI11,
BI12, BI13)
----------------------
-------
Enable In Local
Selects which inputs will be enabled in local mode
Combination of ( BI1, BI2, BI3, BI4,
BI5, BI6, BI7, BI8, BI9, BI10, BI11,
BI12, BI13)
BI1, BI2, BI3,
BI4, BI5, BI6,
BI7, BI8, BI9,
BI10, BI11, BI12,
BI13
Enable In Remote
Selects which inputs will be enabled in remote mode
Combination of ( BI1, BI2, BI3, BI4,
BI5, BI6, BI7, BI8, BI9, BI10, BI11,
BI12, BI13)
BI1, BI2, BI3,
BI4, BI5, BI6,
BI7, BI8, BI9,
BI10, BI11, BI12,
BI13
3.12.2. Function Key Matrix
Description Range Default
Open CB
Selects which function key will Open the circuit breaker
Combination of ( 1, 2, 3, 4, 5, 6 ) ------
Close CB
Selects which function key will Close the circuit breaker
Combination of ( 1, 2, 3, 4, 5, 6 ) ------
79 In/Out
Selects which function key will toggle Autoreclose In & Out
Combination of ( 1, 2, 3, 4, 5, 6 ) ------
79 Trip & Reclose
Selects which function key will cause the CB to trip & reclose
Combination of ( 1, 2, 3, 4, 5, 6 ) ------
79 Trip & Lockout
Selects which function key will cause the CB to trip & lockout
Combination of ( 1, 2, 3, 4, 5, 6 ) ------
Hot Line Work In/Out
Selects which function key will toggle Hot Line Working In &
Out
Combination of ( 1, 2, 3, 4, 5, 6 ) ------
E/F In/Out
Selects which function key will toggle E/F protection In & Out
Combination of ( 1, 2, 3, 4, 5, 6 ) ------
SEF In/Out
Selects which function key will toggle SEF protection In & Out
Combination of ( 1, 2, 3, 4, 5, 6 ) ------
Inst Prot'n In/Out
Selects which function key will toggle Instantaneous protection
elements In & Out
Combination of ( 1, 2, 3, 4, 5, 6 ) ------
Out Of Service Mode Combination of ( 1, 2, 3, 4, 5, 6 ) ------
Local Mode Combination of ( 1, 2, 3, 4, 5, 6 ) ------
Remote Mode Combination of ( 1, 2, 3, 4, 5, 6 ) ------
Local Or Remote Mode
Selects which inputs will put the relay into Local Or Remote
Mode
Combination of ( 1, 2, 3, 4, 5, 6 ) ------