EasyManua.ls Logo

Siemens Argus 7SR21 - Additional Settings

Siemens Argus 7SR21
644 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4 - Data Communications Definitions
© 2017 Siemens Protection Devices Limited Chapter 4 - Page 83 of 96
Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Analog Input Deadband: 34
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input with Flag)
or 2 (16-Bit Analog Input with Flag)
or 3 (32-Bit Analog Input w/o Flag)
or 4 (16-Bit Analog Input w/o Flag)
or 5 (Single Precision, floating point Analog Input with Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o Time)
or 2 (16-Bit Analog Input w/o Time)
or 3 (32-Bit Analog Input with Time)
or 4 (16-Bit Analog Input with Time)
or 5 (Single Precision, floating point Analog Input w/o Time)
or 7 (Single Precision, floating point Analog Input with Time)
Analog Input Reporting Deadband Variation reported when variation 0 requested: 1 (16-Bit)
or 2 (32-Bit)
or 3 (Single Precision, floating point)
Point
Description
Index
185 CB Wear B
Default
Change Event
Assigned Class
(1, 2, 3 or none)
0,3
Default
Variation
Static
Object 30
1
Default
Variation
Event
Object 32
3
Default
Multiplier
0.000
Default
Deadband
1000000.000
186 CB Wear C 0,3 1 3
0.000 1000000.000
187 CB Wear A Remaining 0,3 1 3
1.000
1.000
188 CB Wear B Remaining 0,3 1 3
1.000
1.000
189 CB Wear C Remaining 0,3 1 3
1.000
1.000
190 CB Wear Minimum 0,3 1 3
1.000
1.000
191 Fault Distance Perunit 0,3 5 7
0.001
1.000
196 Frequency Max 0,3 2 4
100.000
1.000
197 S 3P Max 0,3 2 4
0.000 1000000.000
318 Sec Active Power A 0,3 2 4
1.000 10.000
319 Sec Active Power B 0,3 2 4
1.000 10.000
320 Sec Active Power C 0,3 2 4
1.000 10.000
321 Sec P (3P) 0,3 2 4
1.000 10.000
322 Sec Reactive Power A 0,3 2 4
1.000 10.000
323 Sec Reactive Power B 0,3 2 4
1.000 10.000
324 Sec Reactive Power C 0,3 2 4
1.000 10.000
325 Sec Q (3P) 0,3 2 4
1.000 10.000
326 Sec Apparent Power A 0,3 2 4
1.000 10.000
327 Sec Apparent Power B 0,3 2 4
1.000 10.000
328 Sec Apparent Power C 0,3 2 4
1.000 10.000
329 Sec S (3P) 0,3 2 4
1.000 10.000
330 CB Trip Time Meter 0,3 2 4
1000.000
0.010
337 PF 3P Max 0,3 2 4
1000.000
0.100
5.4 Additional Settings
The following relay settings are provided for configuration of the DNP 3.0 implementation when available and are
common to all ports using this protocol.
Setting Name Range/Options Default Setting Notes
Unsolicited
Mode
DISABLED, ENABLED DISABLED As Required
Setting is only visible
when any port
Protocol is set to
DNP3.

Table of Contents

Other manuals for Siemens Argus 7SR21

Related product manuals