7SR21 & 7SR22 Performance Specification
Unrestricted © 2013 Siemens Protection Devices Limited Page 23 of 68
2.3 32 Power
2.3.1 Reference
Parameter Value
Ss 32-n Setting 0.05…2 x Sn
t
d
32-n Delay setting 0.00 … 14400 s
2.3.2 Operate and Reset Level
Attribute Value
S
op
Operate level
100 % Ss, ± 5% or ± 2% Sn
Reset level
Over-power
³ 95 % S
op
Under-power
£ 105 % S
op
Variation
-10 °C to +55 °C
£ 5 %
f
nom
– 3 Hz to f
nom
+ 2 Hz
£ 5 %
2.3.3 Operate and Reset Time
Attribute Value
t
basic
Element basic
operate time
Over-power
1.1 x Ss: 60 ms ± 10 ms
2.0 x Ss: 45 ms ± 10ms
Under-power
0.5 x Ss: 30 ms ± 10ms
t
op
Operate time following delay
t
basic
+ t
d
, ± 1 % or ± 10ms
Disengaging time < 40 ms
2.3.4 Operate Threshold
Attribute Value
Minimum levels for
operation
I 2.5 % In
V 2.5% Vn

Table of Contents

Other manuals for Siemens Argus 7SR21