7SR220 Technical Manual
Chapter 4 - Page 52 of 96 © 2017 Siemens Protection Devices Limited
Address
40001 Time
Address
Description
Format Mult Description
30354 CB Wear A
FP_32BITS_3DP 0.000001 CB Wear A
30356 CB Wear B
FP_32BITS_3DP 0.000001 CB Wear B
30358 CB Wear C
FP_32BITS_3DP 0.000001 CB Wear C
30360 CB Wear A Remaining
FP_32BITS_3DP 1.000000 CB Wear A Remaining
30362 CB Wear B Remaining FP_32BITS_3DP 1.000000 CB Wear B Remaining
30364 CB Wear C Remaining
FP_32BITS_3DP 1.000000 CB Wear C Remaining
30366 CB Wear Minimum
FP_32BITS_3DP 1.000000 CB Wear Minimum
30380 StartCount
FP_32BITS_3DP 1.000000 Start Count
30382 Start Count Target
FP_32BITS_3DP 1.000000 Start Count Target
30392 Active Setting Group UINT16 1.000000 Active Setting Group
30400 Frequency Max
FP_32BITS_3DP 1.000000 Frequency Max
30402 S 3P Max
FP_32BITS_3DP 0.000010 S 3P Max
30444 Sec Active Power A
FP_32BITS_3DP 1.000000 Secondary A Phase W
30446 Sec Active Power B
FP_32BITS_3DP 1.000000 Secondary B Phase W
30448 Sec Active Power C FP_32BITS_3DP 1.000000 Secondary C Phase W
30450 Sec P (3P)
FP_32BITS_3DP 1.000000 Secondary 3 Phase W
30452 Sec Reactive Power A
FP_32BITS_3DP 1.000000 Secondary Phase A VAr
30454 Sec Reactive Power B
FP_32BITS_3DP 1.000000 Secondary Phase B VAr
30456 Sec Reactive Power C
FP_32BITS_3DP 1.000000 Secondary Phase C VAr
30458 Sec Q (3P) FP_32BITS_3DP 1.000000 Secondary 3 Phase VAr
30460 Sec Apparent Power A
FP_32BITS_3DP 1.000000 Secondary Phase A VA
30462 Sec Apparent Power B FP_32BITS_3DP 1.000000 Secondary Phase B VA
30464 Sec Apparent Power C
FP_32BITS_3DP 1.000000 Secondary Phase C VA
30466 Sec S (3P)
FP_32BITS_3DP 1.000000 Secondary 3 Phase VA
30468 CB Trip Time Meter FP_32BITS_3DP 1.000000 CB Trip Time
30482 PF 3P Max
FP_32BITS_3DP 1.000000 Power Factor 3 Phase Max
4.3.4 Holding Registers (Read Write Registers)
Description Format Mult Description
TIME_METER 0.000000 Time