EasyManua.ls Logo

Siemens Argus 7SR21 - Measurands

Siemens Argus 7SR21
644 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7SR220 Technical Manual
Chapter 4 - Page 32 of 96 © 2017 Siemens Protection Devices Limited
FUN INF
Description
ASDU COT
20 Ack, Nak
200 159
User DP Command 2
1 SE
20 Ack, Nak
200 160
User DP Command 3
1 SE
20 Ack, Nak
200 161
User DP Command 4
1 SE
20 Ack, Nak
200 162
200 163
User DP Command 5
User DP Command 6
1 SE
20 Ack, Nak
1 SE
20 Ack, Nak
200 164
User DP Command 7
1 SE
20 Ack, Nak
200 165
User DP Command 8
1 SE
20 Ack, Nak
200 200
CB 1 Trip & Reclose
1 SE
20 Ack, Nak
200 201
200 255
CB 1 Trip & Lockout
Blocked By Interlocking
1 SE
20 Ack, Nak
1 SE, GI
255 0
255 0
General Interrogation (GI) Initiation
General Interrogation (GI) End
7 Init. GI
8 End of GI
255 0
Time Synchronisation
6
Time
Synch.
3.4.2 Measurands
The following Measurand EVT and INF numbers apply to this device.
FUN INF Description
ASDU COT
183 148
Measurand I
L1,2,3,
V
L1,2,3,
P, Q, F, V
L1-2,L2-3,L3-1
---
I
L1
(2.4x) (Window 1%)
I
L2
(2.4x) (Window 1%)
I
L3
(2.4x) (Window 1%)
V
L1
(1.2x) (Window 1%)
V
L2
(1.2x) (Window 1%)
V
L3
(1.2x) (Window 1%)
P (2.4x) (Window 1%)
Q (2.4x) (Window 1%)
F (1.2x) (Window 0.1%)
V
L1-2
(1.2x) (Window 1%)
V
L2-3
(1.2x) (Window 1%)
V
L3-1
(1.2x) (Window 1%)
Cyclic -
Refresh
rate 5
seconds
9
or value
change
greater
than
Window x
%.
183 149
Measurand Power W
1,2,3,
Power VAr
1,2,3,
Power Factor
1,2,3,
---
W
1
(2.4x) (Window 1%)
W
2
(2.4x) (Window 1%)
W
3
(2.4x) (Window 1%)
Cyclic -
Refresh
rate 5
9 seconds
or value
change
greater

Table of Contents