7SR210 Settings Guide
Unrestricted Page 14 of 61 © 2018 Siemens Protection Devices Limited
3.4.4. Measured E/F
Description Range Default
Gn 51G/50G Measurement
Selects whether the RMS value used by the 51G & 50G
elements is True RMS or only calculated at fundamental
frequency
RMS, Fundamental RMS
3.4.4.1. 51G-1
Description Range Default
Gn 51G-1 Element
Selects whether the 51G-1 IDMTL measured Earth Fault
element is enabled
Disabled, Enabled Disabled
Gn 51G-1 Setting
Pickup level
0.005, 0.006 ... 0.995, 1 0.5 xIn
Gn 51G-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL
DTL, IEC-NI, IEC-VI, IEC-EI, IEC-
LTI, ANSI-MI, ANSI-VI, ANSI-EI
IEC-NI
Gn 51G-1 Time Mult (IEC/ANSI)
Time multiplier (applicable to IEC and ANSI curves but not
DTL selection)
0.025, 0.03 ... 1.595, 1.6 , 1.7 ...
4.9, 5, 6 ... 100
1
Gn 51G-1 Delay (DTL)
Delay (applicable only when DTL is selected for characteristic)
0, 0.01 ... 19.99, 20 5 s
Gn 51G-1 Min Operate Time
Minimum operate time of element.
0, 0.01 ... 19.99, 20 0 s
Gn 51G-1 Follower DTL
Additional definite time added after characteristic time
0, 0.01 ... 19.99, 20 0 s
Gn 51G-1 Reset
Selects between an ANSI decaying reset characteristic or DTL
reset
(ANSI) Decaying, 0 ... 59, 60 0 s
Gn 51G-1 Inrush Action
Selects if the 51G-1 element is blocked from operating when
2nd Harmonic Inrush Detector operates
Off, Inhibit Off
3.4.4.2. 51G-2
Description Range Default
Gn 51G-2 Element
Selects whether the 51G-2 IDMTL measured Earth Fault
element is enabled
Disabled, Enabled Disabled
Gn 51G-2 Setting
Pickup level
0.005, 0.006 ... 0.995, 1 0.5 xIn
Gn 51G-2 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL
DTL, IEC-NI, IEC-VI, IEC-EI, IEC-
LTI, ANSI-MI, ANSI-VI, ANSI-EI
IEC-NI
Gn 51G-2 Time Mult (IEC/ANSI)
Time multiplier (applicable to IEC and ANSI curves but not
DTL selection)
0.025, 0.03 ... 1.595, 1.6 , 1.7 ...
4.9, 5, 6 ... 100
1
Gn 51G-2 Delay (DTL)
Delay (applicable only when DTL is selected for characteristic)
0, 0.01 ... 19.99, 20 5 s
Gn 51G-2 Min Operate Time
Minimum operate time of element.
0, 0.01 ... 19.99, 20 0 s
Gn 51G-2 Follower DTL
Additional definite time added after characteristic time
0, 0.01 ... 19.99, 20 0 s
Gn 51G-2 Reset
Selects between an ANSI decaying reset characteristic or DTL
reset
(ANSI) Decaying, 0 ... 59, 60 0 s