7SR210 Settings Guide
Unrestricted ©2018 Siemens Protection Devices Limited Page 27 of 61
Description Range Default
E3 Pickup Delay
Time before equation output operates, after equation satisfied
0, 0.01 ... 14300, 14400 0 s
E3 Dropoff Delay
Time before equation output resets, after equation nolonger satisfied
0, 0.01 ... 14300, 14400 0 s
E3 Counter Target
Select number of times equation must be satisfied before equation
output operates
1, 2 ... 998, 999 1
E3 Counter Reset Mode
Select type of counter reset mode
Off, Multi-shot, Single-shot Off
E3 Counter Reset Time
Select counter reset time
0, 0.01 ... 14300, 14400 0 s
E4 Equation
Enable or Disable logic equation E4
Disabled, Enabled Disabled
E4
Specify logic equations of the form En =
<Operand><Operator><Operand>using the
following:0123456789=Digit() = Parenthesis! = NOT operation. =
AND operation^ = EXCLUSIVE OR operationE(followed by a digit) =
Equation numberF (Followed by a digit) = Function Key
numberI(Followed by a digit) = Binary Input numberL(Followed by a
digit) = LED numberO(Followed by a digit) = output relay
numberV(Followed by a digit) =Virtual Input/Output
number.ExamplesMake a function key LED toggle when function key
is pressed (requires E1 to drive L11 in output matrix)E1 =
F3^L11
(20 Character String)
E4 Pickup Delay
Time before equation output operates, after equation satisfied
0, 0.01 ... 14300, 14400 0 s
E4 Dropoff Delay
Time before equation output resets, after equation nolonger satisfied
0, 0.01 ... 14300, 14400 0 s
E4 Counter Target
Select number of times equation must be satisfied before equation
output operates
1, 2 ... 998, 999 1
E4 Counter Reset Mode
Select type of counter reset mode
Off, Multi-shot, Single-shot Off
E4 Counter Reset Time
Select counter reset time
0, 0.01 ... 14300, 14400 0 s
E5 Equation
Enable or Disable logic equation E5
Disabled, Enabled Disabled
E5
Specify logic equations of the form En =
<Operand><Operator><Operand>using the
following:0123456789=Digit() = Parenthesis! = NOT operation. =
AND operation^ = EXCLUSIVE OR operationE(followed by a digit) =
Equation numberF (Followed by a digit) = Function Key
numberI(Followed by a digit) = Binary Input numberL(Followed by a
digit) = LED numberO(Followed by a digit) = output relay
numberV(Followed by a digit) =Virtual Input/Output
number.ExamplesMake a function key LED toggle when function key
is pressed (requires E1 to drive L11 in output matrix)E1 =
F3^L11
(20 Character String)
E5 Pickup Delay
Time before equation output operates, after equation satisfied
0, 0.01 ... 14300, 14400 0 s
E5 Dropoff Delay
Time before equation output resets, after equation nolonger satisfied
0, 0.01 ... 14300, 14400 0 s
E5 Counter Target
Select number of times equation must be satisfied before equation
output operates
1, 2 ... 998, 999 1