EasyManua.ls Logo

Siemens Argus 7SR21 - Page 258

Siemens Argus 7SR21
644 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7SR220 Settings Guide
Unrestricted ©2018 Siemens Protection Devices Limited Page 53 of 107
Description Range Default
E8
Specify logic equations of the form En =
<Operand><Operator><Operand>using the
following:0123456789=Digit() = Parenthesis! = NOT operation.
= AND operation^ = EXCLUSIVE OR operationE(followed by a
digit) = Equation numberF (Followed by a digit) = Function Key
numberI(Followed by a digit) = Binary Input numberL(Followed
by a digit) = LED numberO(Followed by a digit) = output relay
numberV(Followed by a digit) =Virtual Input/Output
number.ExamplesMake a function key LED toggle when
function key is pressed (requires E1 to drive L11 in output
matrix)E1 = F3^L11
(20 Character String)
E8 Pick-up Delay
Time before equation output operates, after equation satisfied
0, 0.01 ... 14300, 14400 0 s
E8 Drop-off Delay
Time before equation output resets, after equation nolonger
satisfied
0, 0.01 ... 14300, 14400 0 s
E8 Counter Target
Select number of times equation must be satisfied before
equation output operates
1, 2 ... 998, 999 1
E8 Counter Reset Mode
Select type of counter reset mode
Off, Multi-shot, Single-shot Off
E8 Counter Reset Time
Select counter reset time
0, 0.01 ... 14300, 14400 0 s
E9 Equation
Enable or Disable logic equation E9
Disabled, Enabled Disabled
E9
Specify logic equations of the form En =
<Operand><Operator><Operand>using the
following:0123456789=Digit() = Parenthesis! = NOT operation.
= AND operation^ = EXCLUSIVE OR operationE(followed by a
digit) = Equation numberF (Followed by a digit) = Function Key
numberI(Followed by a digit) = Binary Input numberL(Followed
by a digit) = LED numberO(Followed by a digit) = output relay
numberV(Followed by a digit) =Virtual Input/Output
number.ExamplesMake a function key LED toggle when
function key is pressed (requires E1 to drive L11 in output
matrix)E1 = F3^L11
(20 Character String)
E9 Pick-up Delay
Time before equation output operates, after equation satisfied
0, 0.01 ... 14300, 14400 0 s
E9 Drop-off Delay
Time before equation output resets, after equation nolonger
satisfied
0, 0.01 ... 14300, 14400 0 s
E9 Counter Target
Select number of times equation must be satisfied before
equation output operates
1, 2 ... 998, 999 1
E9 Counter Reset Mode
Select type of counter reset mode
Off, Multi-shot, Single-shot Off
E9 Counter Reset Time
Select counter reset time
0, 0.01 ... 14300, 14400 0 s
E10 Equation
Enable or Disable logic equation E10
Disabled, Enabled Disabled

Table of Contents

Other manuals for Siemens Argus 7SR21

Related product manuals