EasyManua.ls Logo

Siemens Argus 7SR21 - Page 358

Siemens Argus 7SR21
644 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7SR21 & 7SR22 Performance Specification
Unrestricted Page 46 of 68 © 2013 Siemens Protection Devices Limited
2.17.3 Operate and Reset Time
Attribute Value
Starter operate time
20 ms, ± 20 ms
t
op
Operate time
char = IEC-NI,
IEC-VI,
IEC-EI,
IEC-LTI
[ ]
Tm
K
t
Is
I
op
´
-
=
1
a
, ± 5 % or ± 30 ms,
for char = IEC-NI : K = 0.14, a = 0.02
IEC-VI : K = 13.5, a = 1.0
IEC-EI : K = 80.0, a = 2.0
IEC-LTI : K = 120.0, a = 1.0
char = ANSI-MI,
ANSI-VI,
ANSI-EI,
[ ]
TmB
A
t
P
Is
I
op
´
ú
ú
û
ù
ê
ê
ë
é
+
-
=
1
, ± 5 % or ± 30 ms,
for char = ANSI-MI : A = 0.0515, B = 0.114, P = 0.02
ANSI-VI : A = 19.61, B = 0.491, P = 2.0
ANSI-EI : A = 28.2, B = 0.1217, P = 2.0
char = DTL
t
d
, ± 1 % or ± t
cycle
Reset time
char = ANSI and
t
res
= DECAYING
[ ]
Tm
R
t
Is
I
res
´
-
=
1
2
, ± 5 % or ± 30 ms,
for char = ANSI-MI : R = 4.85
ANSI-VI : R = 21.6
ANSI-EI : R = 29.1
t
res
¹ DECAYING t
res
, ± 1 % or ± 20 ms
Repeatability
± 1 % or ± 20 ms
Overshoot time < 40 ms
Disengaging time < 50 ms
Variation
f
nom
- 3 Hz
to f
nom
+ 2 Hz
harmonics to f
cutoff
£ 5 %
Figure 2-2 shows the operate times for the four IEC IDMTL curves with a time multiplier of 1. Figure 2-3 and
Figure 2-4 show the ANSI operate and reset curves. These operate times apply to non-directional characteristics.
Where directional control is applied then the directional element operate time should be added to give total
maximum operating time.

Table of Contents

Other manuals for Siemens Argus 7SR21

Related product manuals