Chapter 4 - Data Communications Definitions
© 2017 Siemens Protection Devices Limited Chapter 4 - Page 57 of 96
OBJECT
REQUEST
(Library will parse)
RESPONSE
(Library will respond with)
Object
Number
Variation
Description
Function Codes
(dec)
Qualifier Codes
(hex)
Function
Qualifier Codes
Codes
(hex)
(dec)
10
10
1
2 (default -
see note 1)
Binary Output
Binary Output
Status
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
00, 01 (start-stop)
(response)
17, 28 (index
- see note 2)
2 (write)
1 (read)
00, 01 (start-stop)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
00, 01 (start-stop)
(response)
17, 28 (index
- see note 2)
11 0
Binary Output Change
1 (read)
- Any Variation
06 (no range, or all)
07, 08 (limited qty)
11
11
1
2 (default -
see note 1)
Binary Output Change
1 (read)
without Time
Binary Output Change
1 (read)
with Time
06 (no range, or all)
07, 08 (limited qty)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
17, 28 (index)
130
(unsol. resp)
129
(response)
17, 28 (index)
130
(unsol. resp)
12 0
Control Relay
22 (assign class)
Output Block
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
12 1
3 (select)
Control Relay 4 (operate)
Output Block 5 (direct op)
6 (dir. op, noack)
17, 28 (index)
129
echo of request
(response)
12
12
2
3
3 (select)
Pattern Control
Block
3 (select)
Pattern Mask
7 (limited quantity)
00, 01 (start-stop)
129
echo of request
(response)
129
echo of request
(response)
13
0
Binary Output
Command Event 1 (read)
- Any Variation
06 (no range, or all)
07, 08 (limited qty)
13
1 (default -
see note 1)
Binary Output
Command Event 1 (read)
without Time
06 (no range, or all)
07, 08 (limited qty)
129
(response)
17, 28 (index)
130
(unsol. resp)
13 2
Binary Output
Command Event 1 (read)
with Time
06 (no range, or all)
07, 08 (limited qty)
129
(response)
17, 28 (index)
130
(unsol. resp)
20 0
Binary Counter
- Any Variation
1 (read)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
7 (freeze)
8 (freeze noack)
9 (freeze clear)
10 (frz. cl. noack)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
20 1
32-Bit Binary Counter
1 (read)
(with Flag)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
00, 01 (start-stop)
(response)
17, 28 (index
- see note 2)
20
20
2
3
16-Bit Binary Counter
1 (read)
(with Flag)
32-Bit Delta Counter
(with Flag)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
00, 01 (start-stop)
(response)
17, 28 (index
- see note 2)
20 4
16-Bit Delta Counter
(with Flag)
20
5 (default
see note 1)
32-Bit Binary Counter
1 (read)
(without Flag)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
00, 01 (start-stop)
(response)
17, 28 (index
- see note 2)
4 (operate)
5 (direct op)
6 (dir. op, noack)
4 (operate)
5 (direct op)
6 (dir. op, noack)