Chapter 4 - Data Communications Definitions
© 2017 Siemens Protection Devices Limited Chapter 4 - Page 59 of 96
OBJECT
REQUEST
(Library will parse)
RESPONSE
(Library will respond with)
Object
Number
Variation Description
Function Codes
(dec)
Qualifier Codes
(hex)
Function
Codes
(dec)
Qualifier Codes
(hex)
(unsol. resp)
22 7
32-Bit Delta Counter
Change Event (with Time)
22 8
16-Bit Delta Counter
Change Event (with Time)
23 0
Frozen Counter Event
(Variation 0 is used to
request default variation)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
23
1 (default -
see note 1)
32-Bit Frozen
Counter Event
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
17, 28 (index)
23 2
16-Bit Frozen
Counter Event
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
17, 28 (index)
23 3
32-Bit Frozen Delta
Counter Event
23 4
16-Bit Frozen Delta
Counter Event
23 5
32-Bit Frozen Counter
Event (with Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
17, 28 (index)
(response)
130
(unsol. resp)
129
23 6
32-Bit Frozen Counter
Event (with Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
(response)
130
17, 28 (index)
(unsol. resp)
23 7
32-Bit Frozen Delta Counter
Event (with Time)
23 8
16-Bit Frozen Delta Counter
Event (with Time)
30 0
Analog Input
- Any Variation
1 (read)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
30 1 32-Bit Analog Input 1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
30
2 (default -
see note 1)
16-Bit Analog Input 1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
30 3
32-Bit Analog Input
(without Flag)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
30 4
16-Bit Analog Input
(without Flag)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
30 5 short floating point 1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
30 6 long floating point 1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
31 0
Frozen Analog Input
- Any Variation
31 1
32-Bit Frozen Analog Input
31 2 16-Bit Frozen Analog Input
31 3
32-Bit Frozen Analog Input
(with Time of freeze)
31 4
16-Bit Frozen Analog Input
(with Time of freeze)
31 5
32-Bit Frozen Analog Input
(without Flag)
31 6
16-Bit Frozen Analog Input
(without Flag)