7SR220 Technical Manual
Chapter 4 - Page 72 of 96 © 2017 Siemens Protection Devices Limited
Binary Output Status Points
Static (Steady-State) Object Number: 10
Change Event Object Number: 11
Control Relay Output Blocks (CROB) Object Number: 12
Binary Output Command Event Object Number: 13
Static Variation reported when variation 0 requested: 1 (Binary Output w/o status)
or 2 (Binary Output with status)
Change Event Variation reported when variation 0 requested: 1 (Binary Output Event w/o Time)
or 2 (Binary Output Event with Time)
Command Event Variation reported when variation 0 requested: 1 (Command Status w/o Time)
or 2 (Command Status with Time)
Point
Index
Description
Default
Change
Event
Assigned
Class
(1, 2, 3
or none)
Default
Variation
Static
Object 10
Default
Variation
Event
Object 11
Default
Command
Event
Object 13
Assigned
Class
(1, 2, 3
or none)
Default
Variation
Command
Event
Object 13
CROB
Supported
Operations
Default
CROB
Operations
1 RL 1 0 2 2 0 1
Pulse On
Pulse OnLatch On
Close
Pulse On
2 RL 2 0 2 2 0 1 Latch On Pulse On
Close
3 RL 3 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
4 RL 4 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
5 RL 5 0 2 2 0 1
Pulse On
Pulse OnLatch On
Close
Pulse On
6 RL 6 0 2 2 0 1 Latch On Pulse On
Close
7 RL 7 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
8 RL 8 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
9 RL 9 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
10 RL 10 0 2 2 0 1
Pulse On
Pulse OnLatch On
Close
Pulse On
11 RL 11 0 2 2 0 1 Latch On Pulse On
Close
12 RL 12 0 2 2 0 1
Pulse On
Pulse OnLatch On
Close
Pulse On
13 RL 13 0 2 2 0 1 Latch On Pulse On
Close
14 RL 14 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
33
LED reset, write only
location.
0 2 2 0 1
Pulse On
Latch On
Close
Pulse On