Chapter 4 - Data Communications Definitions
© 2017 Siemens Protection Devices Limited Chapter 4 - Page 81 of 96
Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Analog Input Deadband: 34
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input with Flag)
or 2 (16-Bit Analog Input with Flag)
or 3 (32-Bit Analog Input w/o Flag)
or 4 (16-Bit Analog Input w/o Flag)
or 5 (Single Precision, floating point Analog Input with Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o Time)
or 2 (16-Bit Analog Input w/o Time)
or 3 (32-Bit Analog Input with Time)
or 4 (16-Bit Analog Input with Time)
or 5 (Single Precision, floating point Analog Input w/o Time)
or 7 (Single Precision, floating point Analog Input with Time)
Analog Input Reporting Deadband Variation reported when variation 0 requested: 1 (16-Bit)
or 2 (32-Bit)
or 3 (Single Precision, floating point)
Point
Index
59
Description
Active Power C
Default
Change Event
Assigned Class
(1, 2, 3 or none)
0,3
Default
Variation
Static
Object 30
2
Default
Variation
Event
Object 32
4
Default
Multiplier
0.000
Default
Deadband
1000000.000
60 P (3P) 0,3 2 4
0.000 1000000.000
61 Reactive Power A 0,3 2 4
0.000 1000000.000
62 Reactive Power B 0,3 2 4
0.000 1000000.000
63 Reactive Power C 0,3 2 4
0.000 1000000.000
64 Q (3P) 0,3 2 4
0.000 1000000.000
65 Apparent Power A 0,3 2 4
0.000 1000000.000
66 Apparent Power B 0,3 2 4
0.000 1000000.000
67 Apparent Power C 0,3 2 4
0.000 1000000.000
68 S (3P) 0,3 2 4
0.000 1000000.000
71 Power Factor A 0,3 2 4
1000.000
0.100
72 Power Factor B 0,3 2 4
1000.000
0.100
73 Power Factor C 0,3 2 4
1000.000
0.100
74 Power Factor(3P) 0,3 2 4
1000.000
0.100
75 Act Energy Exp 0,3 1 3
1.000 Disabled
76 Act Energy Imp 0,3 1 3
1.000 Disabled
77 React Energy Exp 0,3 1 3
1.000 Disabled
78 React Energy Imp 0,3 1 3
1.000 Disabled
81 Thermal Status Ph A 0,1 4 4
100.000
1.000
82 Thermal Status Ph B 0,1 4 4
100.000
1.000
83 Thermal Status Ph C 0,1 4 4
100.000
1.000
95 Active Setting Group 0,3 2 4
1.000
1.000
99 Vab Secondary 0,3 2 4
10.000
1.000
100 Vbc Secondary 0,3 2 4
10.000
1.000
101 Vca Secondary 0,3 2 4
10.000
1.000
102 Vn Primary 0,3 2 4
0.010 100.000
103 Vn Secondary 0,3 2 4
10.000
1.000
105 Vx Primary 0,3 2 4
0.010 100.000
106 Vx Secondary 0,3 2 4
10.000
1.000
108 I Phase A Max 0,3 2 4
1.000 100.000
109 I Phase B Max 0,3 2 4
1.000 100.000
110 I Phase C Max 0,3 2 4
1.000 100.000
111 P 3P Max 0,3 2 4
0.000 1000000.000

Table of Contents