7SR210 & 7SR220 Commissioning & Maintenance Guide
Page 66 of 82 © 2013 Siemens Protection Devices Limited
Apply a trip condition by injection of current to cause operation of a suitable protection element. Allow current to
continue after the trip at a level of 110 % of the 50BF Setting current level on any phase. Measure the time for
operation of operation of 50BF-1 Delay and 50BF-2 Delay. Repeat the sequence with current at 90 % of the 50BF
Setting.current level after the element trip and check for no CB Fail operation.
50BF Setting (xIn) Test Current 50BF-1 Delay 50BF-2 Delay
(110%)
(90%) No Operation.. No Operation..
50BF CB Faulty Operation No Delay Operation No Delay
50BF-I4 Setting
(xIn)
Test Current 50BF-1 Delay 50BF-2 Delay
(110%)
(90%) No Operation.. No Operation..
50BF CB Faulty Operation No Delay Operation No Delay
1.1.1.1 Element Blocking
The CB Fail function can be blocked by Binary Input Inhibit. This functionality should be checked.
Element BI Inhibits
50BF