7SR210 & 7SR220 Description of Operation
Unrestricted  Page 74 of 94 ©2018 Siemens Protection Devices Limited
Trip Time Alarm
The CB Trip Time meter displays the measured time between the trip being issued and the CB auxiliary contacts
changing state. If this measured time exceeds the Trip Time Alarm time, a Trip Time Alarm output is issued.
Trip Time Adjust
This allows for the internal delays caused by the relay – especially the delay before a binary input operates – to
be subtracted from the measured CB trip time. This gives a more accurate measurement of the time it took for the
CB to actually trip.
Hot Line In/Out
The Hot Line function can be used to provide an immediate trip and auto-reclose inhibit for any Overcurrent, Earth
Fault or Sensitive Earth Fault detection. This function is used to increase safety when personnel are working in
the vicinity of live primary equipment.
When Hot Line is enabled, pickup of any 50, 51, 50G, 51G, 50SEF or 51SEF element will cause an instantaneous
trip,  bypassing  any  time  delay  setting  of  the  element.  Any  auto-reclose  sequence  will  be  inhibited  and  Auto-
reclose Lockout will be raised. This feature is not triggered by pick-up or operation of other protection elements
such as under/over voltage, frequency, thermal or negative sequence over-current.
Additionally, when Hot Line is In, Manual Close is inhibited. This can help to prevent unintended energisation of a
dead  circuit  whilst  personnel  are  working  nearby.  Hot  Line  must  be  switched  to  Out  before  the  Manual  Close
action will be successful.
Hot  Line  can  be  configured  to  be  switched  In/Out  by  binary  inputs,  function  keys  or  by  commands  via  the
communications protocols. There are no other configurable options for Hot Line.