● Some devices are assigned to corresponding device types automatically (see
chapter Appendix E: Device type list [➙ 138]).
● Create default control logics as per pre-definition.
10.4.2 Configuring the system manually
To modify using 'FC360 Panel Configurator'
1. Connect PC to the panel. See chapter 'Connecting a PC to the panel [➙ 107]'.
2. Open a web browser.
3. Enter web address with 'fc360.siemens.com' and press <Enter>.
'FC360 Panel Configurator' is open.
4. Enter access level 3 password to log into access level 3.
5. Modify configuration as needed.
Generally the following configuration may be modified in 'FC360 Panel
Configurator':
– Customer texts
– Properties and parameter settings
– Allocation of devices and zones
– Control logics
6. After finishing modification, click 'Apply'.
A confirmation window is open.
7. Click 'OK' to download the modified configuration to the panel. (The panel is at
access level 3.)
The panel restarts automatically.
The configuration finishes.