6.11.3 LED indicator (32 zones) (FTO3603-Z1)
Fig. 18: Installation of LED indicator (32 zones)
Function:
The LED indicator (32 zones) shows the actual alarm status of each zone
(max. 32 zones of a panel).
Flashing LED indicates the first zone in alarm.
Static LED on indicates other zones in alarm.
Installation:
Detailed information on installation is available in document A6V11777319. See
chapter 'Applicable documents [➙ 9]'.
Configuration:
No configuration is required.
NOTICE
Before installing the LED indicator (32 zones) on an old panel (FC361-xx),
ensure that you’ve updated the panel software to the latest version. The first
16 LEDs function the same as the replaced LED indicator (16 zones).
You can also install the LED indicator (32 zones) on FC361-YZ or FC361-YA
if the originally-equipped LED indicator (16 zones) needs to be replaced.
If you have an LED indicator (16 zones) at hand, you can install it on any
panel, but don't assign a device to a zone number larger than 16. Otherwise,
the panel displays no alarm status if the device is activated.