Connection factor
The max. number of connectable C-NET peripherals (126 devices per loop) and
the max. line length (3300 m) depend on the device connection factor. Calculation
must be performed first using 'FC360 Cerberus FIT Quantities tool'
(document ID: A6V10885143).
FC360 series don't support silent verification of the expected loop alarm current
and voltage drop margin of an installation. Use 'FC360 Cerberus FIT Quantities
tool' to calculate the load of the C-NET detector line(s).
6.6.1 Connectable C-NET devices
The table below lists all ↑ C NET devices which can be connected to the C-NET
↑ detector line(s). It also highlights the devices with an ↑ alarm indicator (AI), or
with an ↑ external alarm indicator (EAI) or a sounder base (DBS720) that can be
connected to the devices.
not possible/not available
Heat detector (static+ROR)
Heat detector (static) with temperature report
support
Multi-sensor smoke detector
Multi-sensor smoke detector;
DualProtocol Collective
Heat detector (static+ROR)
Multi-sensor smoke detector
Infrared flame detector (2 sensors/1 photo diode);
DualProtocol Collective
Linear smoke detector; DualProtocol Collective
Neural fire and CO detector with ambient
supervision
Manual call point, direct action
Manual call point, indirect action
Manual call point, direct action
Manual call point, direct action
Manual call point, direct action
Manual call point, direct action
Zone module, ext. powered (1 collective line)
Input/output module (1 input and 1 output)