Installation
Accessories
6
A6V10421795_en--_k
47 | 151
6.11.2 Evacuation module (FTO3601-H1) [NL]
Fig. 16: Installation of evacuation module (NL)
Function:
The evacuation module (NL) provides the Dutch special function. It activates all
sounder lines and alarm devices of 'EVAC siren' and 'EVAC voice' types by
pressing the <START> button twice and deactivates these devices by pressing the
<STOP> button twice. Once activated, alarm devices on sounder lines play the
'Continuous' tone, EVAC voice devices make the sound following the pre-set audio
sequence ('Continuous' tone --> voice message), and EVAC siren devices play the
tone configured in 'Addressable sounders tone 1' under task card ‘Site’ in FC360
Panel Configurator.
Installation:
Detailed information on installation is available in document A6V10431009. See
chapter 'Applicable documents [➙ 9]'.
Configuration:
The evacuation module (NL) is configured by default when starting up with country
setting 'NL: With FTO3601 H1 (EVAC field)'.
Operation:
Fig. 17: PMI of evacuation module (NL)
No.
Description
Status
Function
1
LED: EVAC
devices active
On
Devices of 'EVAC siren' and 'EVAC voice'
types are activated.
2
LED: EVAC fault
Flashing
One or more alarm devices are in fault.
On
All alarm devices are disabled.
3
Button: 'START'
-
Press twice quickly to start all alarm devices.
4
Button: 'STOP'
-
Press twice quickly to stop all alarm devices.
FTO3601-H1
Ontruimingsalarm
2x Start
2x Stop
Storing
3
4
1
2