System description
Technical data
4
A6V10421795_en--_k
23 | 151
4.4.2 Electrical data
Rating detector line
Operating voltage
DC 12…33 V
Operating current
Max. 0.5 A
Line resistance/capacitance
Max. 240 Ω/Max. 500 nF
Monitored for earth fault
Yes
Monitored for open/short circuit
Yes
Sounder lines on mainboard
Voltage/current
DC 24 V/0.5 A
1
EOL element
Resistor 2.2 kΩ/1 W/0.5 %
AUX. power output
DC 24 V/0.2 A
Configurable IOs on mainboard
Voltage/current
DC 24 V/0.1 A
2
Outputs on output card (4M) FCA3602-Z1
Voltage/current (max. per output)
DC 24 V/1.0 A
3
EOL element
Resistor 2.2 kΩ/1 W/0.5 %
Additionally for outputs on output card (4M) FCA3602-Z1 with the
functionality ‘creeping open/short’
Line resistance
Max. 74.3 Ω
Sounder voltage
Min. DC 16 V
Relay outputs on mainboard
DC 60 V/2.0 A
Power supply
Mains voltage
AC 97…127 V
AC 196…253 V
Mains fuse
AC 250 V/2.5 AT
Power consumption
70 W
Max. nominal output current with battery
charging, I
max a
0.9 A
Max. nominal output current without battery
charging, I
max b
2.5 A
Min. output current
0.05 A
System supply voltage
DC 20.5…28.6 V
Mains failure delay
1 min., 5 min., 10 min., 29 min.
Battery low discharge cut off
DC 20.5…21 V
Temperature compensation
Yes