8 Operation
This chapter describes detailed operation workflow on important fire detection
system functions.
8.1 Alarm procedure in unmanned mode
Display provides fire information. See chapter 'Event views [➙ 66]'.
Immediate activation of panel states 'Any fire' and 'Global alarm'.
If configured: RT fire is activated by 'Global alarm'.
Press <Acknowledge> to confirm
attendance.
(Access level 2 password is required.)
→ Buzzer is off.
Optional: Press <Silence/Resound> to
silence/resound all alarm devices.
Read the alarm event information on the LCD and
go to the indicated fire location to verify the incident.
Examine the fire location and decide whether it is a MAJOR INCIDENT or MINOR
INCIDENT.